TABLE 1 - Characteristics defined by the CEI 70-1 - IEC 529 - IEC 144 - UTE C 20-010 - DIN 40050 Standards

IP_0 to IP_4 || IP_5 to IP_8 || Table 2

First Digit - Protection against persons - touching and ingress of solid objects Second Digit - Protection against the penetration of liquids
IP_5 IP_6 IP_7 IP_8
 
Protection against water jets from any direction (360ยบ) Protection against heavy seas (waves) Protection against effects of immersion in water under defined conditions of pressure and time  Protection against continuous submersion in water 
   
IP_0   Without Protection        
IP_1 Protection against touching with the hand and solid objects greater than 50mm dia.        
IP_2 Protection against touching with the finger and solid objects greater than 12mm dia.        
IP_3 Protection against touching with tools, wires, etc, more than 2.5mm thick and solid objects greater than 2.5mm dia.        
IP_4 Protection against touching with tools, wires, etc, more than 1mm thick and solid objects greater than 1mm dia.        
IP_5 Unlimited protection against contact with live parts and damaging deposits of dust IP 55      
IP_6 Unlimited protection against contact with live parts and any protection of dust IP 65 IP 66 IP 67 IP 68

In some countries a third digit (for mechanical security) is added.