| ELECTRICAL |
Insulation Resistance
Per IEC 309-1, Clause 19 |
500V
for 1 min. Resistance
5M  |
Dielectric Strength
Per IEC 309-1, Clause 19 |
3000V
for 1 min. |
Norm. Operation,
Connect & Disconnect Cycles
Per IEC 309-1, Clause 21 |
See
Table 1 |
Breaking Capacity
Per IEC 309-1, Clause 20 |
Tested
at 110% of the rated operating voltage and 125% of the rated current. |
Temperature Rise
Per IEC 309-1, Clause 22 |
Maximum
50 K rise at full rated current. |
| MECHANICAL |
Cable Secureness
Per IEC 309, Clause 23 |
See
Table 2 |
Impact
Per IEC 309, Clause 24 |
A
device is wired with a 2.25m length of flexible cord and dropped from a
height of 75 cm, 8 times. The device is then tested for applicable degrees
of protection against moisture. |
| ENVIRONMENTAL |
| Flammability |
Self-extinguishing
Per IEC 309-1, Clause 27 |
| Ambient Temperature
Range |
Minimum:
-25º C with impact
Maximum: 90º C |
| Moisture Resistance |
Watertight
(IP67): Device immersed for 24 hours in water at a temp. of 25º C, the highest
point of the device being 5cm (2") below the water level.
Splashproof (IP44): Device is sprayed with water for 10 minutes and immediately
afterwards subjected to splashing water in all directions (360º). |
| UV Resistance |
Exposed
plastic materials are UV stabilized. |
TABLE 1
|
Connect
and Disconnect Cycles
|
| Device
Rating Amperes |
Cycles
with Load at Rated Current and Voltage |
No-Load
Cycles |
Sequence |
16
32
63
125 |
5000
p.f. of 0.6
1000 p.f. of 0.6
1000 p.f. of 0.6
250 p.f. of 0.7 |
0
1000
1000
250 |
-
Alternating
Alternating
Alternating |
|
The test sequence is conducted by using
a no-load, followed by a load sequence.
TABLE 2
|
Cable
Secureness Test
|
| Device
Rating Amperes |
Force |
Torque |
Maximum
Displacement |
| N |
 |
mm |
16
32
63
125 |
80
100
120
200 |
0.350
0.425
0.8
1.5 |
2
2
2
2 |
|
The flexible cord or cable is twisted
and pulled. Values for the applied twisting torque and force of pull are shown
in Table 2. In all cases the cord displacement is less than 2mm.

DECLARATION OF
CONFORMITY
WALTHER
WERKE, Ferdinand Walther GmbH
Ramsener Strasse 6
67304 Eisenberg
We declare,
under our sole responsibility, the conformity of the following products and
standards:
Plugs and
Sockets (Pin and Sleeve devices)
DIN EN 60 309, T. 1/BS 4343
DIN EN 60 309, T. 2
This declaration
of conformity is according to the EC regulations 73/23, 91/368 and 89/336 (Low
Voltage Directive), module A, in consideration of DIN EN 45 014.


|
DIN EN ISO 9001
|
|
Certificate
Registration No. 4678-01 |
|