IEC 309 PIN & SLEEVE DEVICES
- INTERNATIONAL RATINGS -

ELECTRICAL
Insulation Resistance
Per IEC 309-1, Clause 19
500V for 1 min. Resistance 5M
Dielectric Strength
Per IEC 309-1, Clause 19
3000V for 1 min.
Norm. Operation, Connect & Disconnect Cycles
Per IEC 309-1, Clause 21
See Table 1
Breaking Capacity
Per IEC 309-1, Clause 20
Tested at 110% of the rated operating voltage and 125% of the rated current.
Temperature Rise
Per IEC 309-1, Clause 22
Maximum 50 K rise at full rated current.

MECHANICAL
Cable Secureness
Per IEC 309, Clause 23
See Table 2
Impact
Per IEC 309, Clause 24
A device is wired with a 2.25m length of flexible cord and dropped from a height of 75 cm, 8 times. The device is then tested for applicable degrees of protection against moisture.

ENVIRONMENTAL
Flammability Self-extinguishing
Per IEC 309-1, Clause 27
Ambient Temperature Range Minimum: -25º C with impact
Maximum: 90º C
Moisture Resistance Watertight (IP67): Device immersed for 24 hours in water at a temp. of 25º C, the highest point of the device being 5cm (2") below the water level.
Splashproof (IP44): Device is sprayed with water for 10 minutes and immediately afterwards subjected to splashing water in all directions (360º).
UV Resistance Exposed plastic materials are UV stabilized.

TABLE 1
Connect and Disconnect Cycles
Device Rating Amperes Cycles with Load at Rated Current and Voltage No-Load Cycles Sequence
16
32
63
125
5000 p.f. of 0.6
1000 p.f. of 0.6
1000 p.f. of 0.6
250 p.f. of 0.7
0
1000
1000
250
-
Alternating
Alternating
Alternating

The test sequence is conducted by using a no-load, followed by a load sequence.
TABLE 2
Cable Secureness Test
Device Rating Amperes Force Torque Maximum Displacement
N Nom mm
16
32
63
125
80
100
120
200
0.350
0.425
0.8
1.5
2
2
2
2

The flexible cord or cable is twisted and pulled. Values for the applied twisting torque and force of pull are shown in Table 2. In all cases the cord displacement is less than 2mm.

C E

DECLARATION OF CONFORMITY

WALTHER WERKE, Ferdinand Walther GmbH
Ramsener Strasse 6
67304 Eisenberg

We declare, under our sole responsibility, the conformity of the following products and standards:

Plugs and Sockets (Pin and Sleeve devices)